Housing/
Cover material: |
|
PPE/PA/PSU transparent
|
|
Control air and ambient
temperature: |
|
-10... +50 °C |
|
Control medium: |
|
Quality classes to DIN
ISO 8573-1 |
|
Control air connection: |
|
G 1/4, NPT_on request |
|
Supply
pressure*: |
|
3... 7 bar |
|
Flow capacity QNn: |
|
100 L/min |
|
Intrinsic air
consumption: |
|
0 L/min |
|
Operating voltage: |
|
24 V DC +/-
10% |
|
Residual ripple: |
|
10% not industrial DC |
|
Power consumption : |
|
< 5 W |
|
Electrical connection: |
|
3 bushings (M16x1,5,
screw terminals) |
|
Set point setting: |
|
0/4... 20 mA; 0...5/10 V |
|
Input
resistance for setpoint signal: |
|
180 Ohm bei 0/4 - 20 mA
19 kOhm bei 0…..5/10 V |
|
Sensor Inputs for process
controller |
|
4... 20 ma PT100,
frequency |
|
Input
resistance for process value signal |
|
180 Ohm with 0/4 - 20 mA
19 kOhm with 0... 5/10 V |
|
Lift turn: |
|
5... 45 mm |
|
Options:
|
|
2 binary outputs,
inductive proximity switches, analog
feedback, process controller |
|
Bus communication: |
|
Profibus DP or DeviceNet |
|
Operating panel and
configuration: |
|
Module with 3 keys for
parametrization |
|
Display for setpoint and
process value: |
|
8-digit, 16 segment LC
display |
|
Type of protection: |
|
IP65 to EN 60529 |
|
Conformity: |
|
CE to EMV-9/336/EWG |
| |
|
*Pressure stated in bar:
are excess to atmosphere |